• For data storage registers, a boundary error occurs if the specified area (start register + register
range) does not exist in either the local or remote ports.
Local port: TermSTS = 0AH, remote port: TermSTS = 8AH
• A response timeout error (TermSTS = 02H) occurs if the response time from the remote port
exceeds the time specified by the timer counter value.
• Read protection can be specified for each register type on the local T2N by using the special
coil settings described below. In this case, a memory write protect error (TermSTS = 04H) will
occur.
F 9 8 7 6 5 4 3 2 1 0
SW067 SW C T F D RW LW W XW/YW
• When PC link transmission or the UDP socket interface is used, if an application
transmits to a nonexistent remote port, an transmission error (TermSTS = 0BH, detailed
information = 0020H) occurs.
0:Write enabled
1:Write protected
Special registers
Counter registers
Timer registers
PC internal file registers
Expansion file registers (IC card)
Input/output registers
Link registers
Link relay registers
Auxiliary registers
Data registers