c. Status (See figure 4.3 for details on bits C, D, E and F.)
F E D C B A 9 8 7 6 5 4 3 2 1 0
B 0 0 0 0 TermSTS
B+1 Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
This request can be used in run and standby modes.
The read out RAS information is stored in the specified register area as shown below.
RAS information
word count
Specified register start address
RAS information
A register area whose size is the size of the read out
RAS information plus one word must be allocated.
A boundary error (TermSTS = 0AH) occurs if it is not possible to allocate an area that is the
size of the read out RAS information plus one word for the RAS information storage area.
A parameter error (TermSTS = 03H) occurs on any of the following transfer parameter
settings.
If the RAS request type (Kind) is out of range (a value other than 1 to 5).
If the start position (Start) is out of range (a value of 4 or larger) for MIB information.
If the start position (Start) is out of range (a value of 161 or larger) for event trace
information.
If the read count (ReadCnt) is out of range (a value of 31 or larger) for event trace
information.