American Dryer Corp. ADG-530D II Clothes Dryer User Manual


 
27
2.
Technical Gas Data
a. Gas Specifications
b. Gas Connections:
Inlet connection ------------3/4” N.P.T.
Inlet supply size ------------3/4” N.P.T. (minimum)
Btu/hr input (per dryer) ---204,000 (51,408 kcal/hr)
Btu/hr input (per pocket) --102,000 (25,704 kcal/hr)
1) Natural Gas
Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure
must be consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches
(29.9 mb) of water column (W.C.) pressure.
2) Liquid Propane (L.P.) Gas
Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so
that the gas pressure must be regulated upstream of the dryer. The pressure measured at each
gas valve pressure tap must be a consistent 10.5 inches (26.1 mb) of water column. There is no
regulator or regulation provided in an L.P. dryer. The water column pressure must be regulated at
the source (L.P. tank) or an external regulator must be added to each dryer.
Natural Gas .............................. #10 = 0.1935” (4.1949 mm).
Liquid Propane Gas .................. #33 = 0.1137” (2.8880 mm).
TYP E OF GAS
NATURAL LIQUID PROPANE
Manifold Pressure* 3.5 inches W.C. 8.7 mb 10.5 inches W.C. 26.1 mb
In-Line Pressure 6.0 - 12.0 inches W.C.
14.92 - 29.9 mb 11.0 inches W.C. 27.4 mb
Shaded areas are stated in metric equivalents
* Measured at gas valve pressure tap when the gas valve is on.
TYP E OF GAS
L.P.
Conversion
Kit
Part Number
ADC
MODEL
NUMBER
BTU
Per Hour
Rating
kcal/hr
Rating
Natural Liquid Propane
Qty. D.M.S.*
Part
Number
Qty. D.M.S.*
Part
Number
ADG-530D
204,000
51,408
2 #10 140836 2 #33 140855 881119
(T
OTAL
F
OR
B
OTH
B
ASKETS
)
Shaded area is stated in metric equivalent
* Drill Measurement Size (D.M.S.) equivalents are as follows: