54
Sprinkler Option Temperature Controller Settings
NOTE: Refer to Controller’s User’s Manual for further information on controller options.
Note: When message display (Cy) set to OnOF.
SPOL (SET POINT OUTPUT LOW LIMIT) not in use.
SPOH (SET POINT OUTPUT HIGH LIMIT) not in use.
Are not displayed.
Message
Display
Message
Description
Settings
SECr SECURITY CODE
FULL SECURITY - SET TO 110 (DISPLAYED AS 1) "VIEW
ONLY"
NO SECURITY - SET TO 111 (DISPLAYED AS 4)
"ALL FEATURES UNLOCKED"
InP INPUT DEVICE P 385 = RTD INPUT
F-C º F OR º C SELECT TYPE REQUIRED (FAHRENHEIT OR CELSIUS)
dPt DECIMAL POINT 0, NO DECIMAL POINT
InPt INPUT FAULT TIMER 0.2
SPL SET POINT LOW 500 (SETTING CANNOT BE LOWER)
SPH SET POINT HIGH 700 (SETTING CANNOT BE HIGHER)
SPSt SET POINT STATE rE (REVERSE ACTION)
SPLP SET POINT LAMP 0 oFF (LAMP OFF WHEN OUTPUT IS ON)
AL HIGH ALARM ONLY Hi
ALt ALARM TYPE Abs (ABSOLUTE ALARM)
ALrE ALARM RESET OnOF (AUTOMATIC RESET)
ALPi
ALARM POWER
INTERRUPT
OFF (ALARM INHIBIT IS OFF)
ALiH ALARM INHIBIT OFF (ALARM INHIBIT IS OFF)
ALSt
ALARM OUTPUT
STATE
CLOS
(CLOSES CONTACTS AT ALARM SET POINT)
ALLP ALARM LAMP
0 ON (ALARM LAMP IS ON WHEN ALARM CONTACT IS
CLOSED)
ALHi ALARM HI 650º F OR 343.3º C (NOTE: ADJUST SAME AS SP)
Cy CYCLE RATE OnOF
SP_d
SET POINT ON-OFF
DIFFERENTIAL
-1
rt RAMP TIME OFF
InPC INPUT CORRECTION 0
FiLt DIGITAL FILTER 2
SP
TEMPERATURE
SET POINT
650º F OR 343.3º C