18 American Dryer Corp. 113386-14
To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward
should be installed where the exhaust exits the building. If the exhaust ductwork travels vertically up
through the roof, it should be protected from the weather by using a 180° turn to point the opening
downward. In either case, allow at least twice the diameter of the duct between the duct opening and
nearest obstruction.
IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust
ductwork.
14-INCHES (35.56 CM) DIAMETER, 2,150 CFM (60.88 CMM)
EXHAUST CONNECTION AT COMMON DUCT
(GAS, ELECTRIC, AND STEAM MODELS)
!