American Dryer Corp. AD-120ES Clothes Dryer User Manual


 
113386-14 www.amdry.com 13
D. FRESH AIR SUPPLY REQUIREMENTS
When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and
exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the
make-up air is inadequate, drying time and drying efficiency
will be adversely affected. Ignition problems and
sail switch “fluttering” problems may result, as well as premature motor failure from overheating.
Air supply (make-up air) must be given careful consideration to ensure proper performance of each dryer. An
unrestricted source of air is necessary for each dryer. An airflow of 2,150 cfm (cubic feet per minute)
(60.88 cmm [cubic meters per minutes]) must be supplied to each dryer. As a general rule, an unrestricted air
entrance from the outdoors (atmosphere) of a minimum of 3 square feet (0.28 square meters) is required for
each dryer.
To compensate for the use of registers or louvers used over the openings, the area must be increased by
approximately thirty-three percent (33%). Make-up air openings should not be located in an area directly near
where exhaust vents exit the building.
It
is not necessary to have a separate make-up air opening for each dryer. Common make-up air openings are
acceptable. However, they must be set up in such a manner that the make-up air is distributed equally to
ALL
the dryers. The dryer must be installed with provisions for adequate combustion and make-up air supply.
EXAMPLE: For a bank of six (6) gas dryers, two (2) openings measuring 3 feet by 3 feet
(0.91 meters by 0.91 meters) are acceptable.
Allowances must be made for remote or constricting passageways or where dryers are located at excessive
altitudes or predominantly low pressure areas.