Installation
28
F232058
Electrical Installation (Continued)
Electrical Specifications
Voltage Designation Standard Electric Heat
Model
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Breaker
AWG
mm
2
Full Load
Amps
Breaker
AWG
mm
2
35
M 550-575 50-60 3 3 4 15 14 3x2.5 Not available in this voltage.
M* 550-575 50-60 3 3 6 10 14 3x2.5 Not available in this voltage.
N 440-480 50-60 3 3 4 15 14 3x2.5 32 35 8 3x10
N* 440-480 50-60 3 3 6 15 12 3x4 25 30 10 3x6
P 380-415 50-60 3 3 4 15 14 3x2.5 32 35 8 3x10
P* 380-415 50-60 3 3 6 15 12 3x4 22 30 10 3x6
Q 200-240 50-60 3 3 10 15 14 3x2.5 50 50 8 3x10
Q* 200-240 50-60 3 3 10 20 12 3x4 38 50 6 3x16
T 200-240 50-60 1 2 13 15 14 2x2.5 Not available in this voltage.
T* 200-240 50-60 1 2 19 30 10 3x6 Not available in this voltage.
50
M 550-575 50-60 3 3 6 15 14 3x2.5 Not available in this voltage.
M* 550-575 50-60 3 3 10 15 14 3x2.5 Not available in this voltage.
N 440-480 50-60 3 3 4 15 14 3x2.5 43 50 8 3x10
N* 440-480 50-60 3 3 11 20 12 3x4 38 50 6 3x16
P 380-415 50-60 3 3 4 15 14 3x2.5 43 50 8 3x10
P* 380-415 50-60 3 3 11 20 12 3x4 33 40 8 3x10
Q 200-240 50-60 3 3 10 15 14 3x2.5 76 80 4 3x25
Q* 200-240 50-60 3 3 19 30 10 3x6 56 70 4 3x25
T 200-240 50-60 1 2 18 25 10 2x6 Not available in this voltage.
T** 200-240 50-60 1 2 26 50 6 2x16 Not available in this voltage.
85
M** 550-575 60 3 3 13 25 10 3x4 Not available in this voltage.
N** 440-480 50-60 3 3 13 25 10 3x4 55 60 6 3x16
P** 380-415 50-60 3 3 13 25 10 3x4 55 60 6 3x16
Q** 200-240 50-60 3 3 24 40 8 3x6 105 110 2 3x35
Note: Wire sizes shown are for copper, THHN, 90° conductor per NEC article 310.
*Models with 1305-series drive.
**Models with 1336-series drive.