Alliance Laundry Systems Stacked Drying Tumbler Clothes Dryer User Manual


 
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Installation Instructions
13
M412060
Individual Exhaust
Collector Duct
Figure 1
VERTICAL EXHAUST INSTALLATION HORIZONTAL EXHAUST INSTALLATION
180°
Sweep Elbow
No Screen
or Cap
2 in (5.1 cm)
Minimum
Clearance
30 in (76.2 cm)
Minimum
Clearance
0 in
Clearance
Permitted
for First
4 in
(10.2 cm)
12 in (30.5 cm)
Minimum
Clearance
0 in Clearance
Permitted
for First
4 in (10.2 cm)
12 in (30.5 cm)
Minimum
Clearance
2 in (5.1 cm)
Minimum
Clearance
No
Screen
Or
Cap
Wall
NOTE: Maximum length
of exhaust duct is 14
feet (4.3 meters).
NOTE: Maximum length
of exhaust duct is 14
feet (4.3 meters).
Clearance permitted to combustible material
36 in (91.4 cm) recommended for maintenance purposes
24 in (61.0 cm) minimum
Wall
TMB2153N
30 in (76.2 cm)
Minimum
Clearance
Figure 2
2 in
(5.1 cm)
Minimum
Clearance
30 in (76.2 cm)
Minimum Clearance
2 in (5.1 cm) Minimum Clearance
2 in (5.1 cm)
Minimum
Clearance
No Screen
or Cap
Wall
Air Out
Inspection or
Cleanout
Cover
31.62 in
(80.3 cm)
L Dia K Dia J Dia I Dia H Dia G Dia F Dia E Dia D Dia C Dia B Dia A Dia
Ceiling
180°
Sweep Elbow
NOTE: This collector duct is sized for individually
ducted units as shown. Refer to Figure 1.
Where the exhaust duct pierces the wall or ceiling, an
opening having a diameter four inches larger than the
diameter of the exhaust duct shall be provided, and the
exhaust duct centered within the opening.
Duct
Station
Min. Diameter
for Individual
Exhaust
Duct
Station
Min. Diameter
for Individual
Exhaust
A
7.00 in (17.8 cm)
G
19.00 in (48.3 cm)
B
10.00 in (25.4 cm)
H
20.00 in (50.8 cm)
C
12.00 in (30.5 cm)
I
22.00 in (55.9 cm)
D
14.00 in (35.6 cm)
J
23.00 in (58.4 cm)
E
16.00 in (40.6 cm)
K
24.00 in (61.0 cm)
F
18.00 in (45.7 cm)
L
25.00 in (63.5 cm)
TMB2154N