GROUNDING INSTRUCTIONS
Drying tumbler must be grounded. In event of malfunction or breakdown, grounding will reduce risk of electric
shock by providing a path of least resistance for electric current. Drying tumbler must be connected to a
grounded metal, permanent wiring system; or an equipment grounding conductor must be run with circuit
conductors and connected to the PE Busbar.
WARNING
To reduce the risk of fire and electric shock, check with a qualified service technician
for proper grounding procedures. Improper connection of the equipment grounding
conductor can result in a risk of electric shock.
WARNING
To reduce the risk of fire and electric shock, if electrical supply is coming from a three
phase service, DO NOT connect a Stinger Leg to a single phase machine.
Figure 14
LOW PRESSURE STEAM DRYING TUMBLERS
240 V
1 Phase, 50 Hz.
Minimum Wire Size 14 AWG (2.081 mm²)
Circuit Breaker 15 AMP
Poles 2