5-08-51
Electrical Installation Requirements - Model IWF075 (M-speed)
Only trained personnel should perform this
procedure. Use caution while servicing
machines with covers removed and power
applied.
W700
WARNING
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Recommended
Circuit Breaker
(US-market)
AWG/mm
2
kW Standard
Heating Elements
Full Load
Amps
Recommended
Circuit Breaker
(US-market)
AWG/mm
2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 7 15 10 14/2.5
6x4 kW
42 50 50
8/10.0
P 380-415 50/60 3 3+N+PE 25 30 30 10/6.0 60 70 70
4/25.0
Q 200-240 50/60 3 3+PE 25 30 30 10/6.0
6x3 kW
70 80 80
4/25.0
X 200-240 50/60 1/3 2/3+PE 25 30 30 10/6.0 N/A N/A N/A
N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x3 kW
+
3x4 kW
38 50 50
8/10.0
P 380-415 50/60 3 3+N+PE 55
70 70
4/25.0
Q 200-240 50/60 3 3+PE
N/A
N/A N/A
N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A
N/A
Table 16