American Dryer Corp. D30 Clothes Dryer User Manual


 
20 JLA Limited 113239-5
2. Electrical Service Specifications
IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact the
factory.
a. Gas and Steam Models Only
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
100 2 8.0 9.4 15
115 2 8.7 15
208 2 5.2 15
230 2 4.8 15
240 2 5.6 15
208 3 3.0 15
230 3 3.2 15
240 3 3.6 15
380-400 4* 2.2 15
416 4* 2.3 15
460-480 3 2.1 15
* 3-Wire is available. 9/2/08
b. Electric Models Only
ALL electrically heated dryers must
be connected to the electric service
shown on the dryer’s data label. The
connecting wires must be properly
sized to handle the rated current.
* 3-Wire is available. 9/2/08
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
208 15 kW 2 77 100
230
15 kW 2 70 90
240
15 kW 2 68 90
380
15 kW 4* 29 40
208
20 kW 2 101 150
230
20 kW 2 92 125
240
20 kW 2 89 125
208
20 kW 3 62 80
380
20 kW 4* 34 45
416
20 kW 4* 32 45
400
22 kW 4* 39 80
208
24 kW 3 72 90
220
24 kW 3 66 90
230
24 kW 3 65 90
240
24 kW 3 63 80
380
24 kW 4* 42 60
416
24 kW 4* 39 50
460
24 kW 3 32 40