American Dryer Corp. D30 Clothes Dryer User Manual


 
113239-5 01422 822282 15
NOTE: As per the National Fuel Gas Code, “Exhaust ducts for Type 2 clothes dryers shall be
constructed of sheet metal or other noncombustible material. Such ducts shall be equivalent in
strength and corrosion resistance to ducts made of galvanized sheet steel not less than 26
gauge (0.0195-inches [0.50 mm]) thick.”
SINGLE DRYER VENTING
IMPORTANT: For exhaust duct runs over 85 feet (25.9 meters) a minimum size of 10-inches (25.4
cm) must be used.
HORIZONTAL VENTING
When a single 8-inch (20.32 cm) horizontal vent is used, the ductwork to the outlet cannot exceed 85 feet
(25.9 meters), refer to Illus. A below. This calculation of 85 feet (25.9 meters) compensates or allows for the
use of a maximum of only one (1) elbow (which is the outside outlet protection).
Illus. A