American Dryer Corp. AD-200 Clothes Dryer User Manual


 
19
WARNING: 208 VAC and 230 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
IMPORTANT: The dryer must be connected to the electrical supply shown on the data label
that is affixed to the back of the dryer, at the upper right hand corner. In case
of 208 VAC or 230/240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation..
ADS-200 (STEAM )
15 HP BLOWER/3 HP DRIVE M OTOR
ELECTRIC SERIVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual element-time delay-current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size
according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP
DRAW
MINIMUM
WIRE
SIZE*
FUSING
Dual ElementTime Delay
CIRCUIT
BREAKER
60 Hz 50 Hz 60 Hz 50 Hz
208 3/4 55 --- 4 80 --- 90
230/240 3 49 --- 4 80 --- 90
380/400 3/4 --- 29 10 --- 40 60
416 3/4 --- 27 10 --- 40 60
460/480 3/4 26 --- 10 40 --- 60
* AWG Stranded Type Wire...for individual lengths less than 100 feet (30.48 meters).