American Dryer ML-200 Clothes Dryer User Manual


 
18
2.
Electrical Service Specifications
WARNING: 208 VAC and 230 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
IMPORTANT: The dryer must be connected to the electrical supply shown on the data label that
is affixed to the back of the dryer, at the upper right hand corner. In case of 208 VAC
or 230 VAC, the supply voltage must match the electric service specifications of the
data label exactly.
NOTE: ADC RESERVES THE RIGHT TO MAKE CHANGES IN SPECIFICATIONS AT ANY
TIME, WITHOUT NOTICE or OBLIGATION.
MLG-200 (Gas)
7.5 Hp Blow er/3 Hp Drive Motor
E
LECTRIC
S
ERVICE
S
PECIFICATION
(
PER DRYER
)
IMPORTANT:
208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES
: A. Fuse ratings are dual element-time delay-current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3
Ø
dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE
SIZE*
FUSING
Dual Element
Time Delay
CIRCUIT
BREAKER
60 Hz 50 Hz
208 3Ø 3/4 37 --- 4 60 80
230 3Ø 336--- 4 60 80
380 3Ø 3/4 --- 20 8 30 40
416 3Ø 3/4 --- 19 8 30 40
460 3Ø 3/4 18 --- 8 30 40
* AWG Stranded Type Wire...for individual lengths less than 100 feet (30.48 meters).