Specifications and Dimensions
F8138601
50
100
Q
(Through
4/13/10)
200 – 240 50/60 3 3 10 15 14 2.5 108 110 1 50
Q
(Starting
4/14/10)
200 – 240 50/60 3 3 14 20 14 2.5 108 110 1 50
R
(Through
10/1/10)
380 – 480 50/60 3 3 10 15 14 2.5 40 50 6 16
N
(Starting
10/4/10)
440 – 480 50/60 3 3 10 15 14 2.5 40 50 6 16
P
(Starting
10/4/10)
380 – 415 50/60 3 3 10 15 14 2.5 40 50 6 16
125
Q 200 – 240 50/60 3 3 9 15 14 2.5
NOT AVAIL ABLE
R
(Through
10/1/10)
380 – 480 50/60 3 3 8 15 14 2.5
N
(Starting
10/4/10)
440 – 480 50/60 3 3 8 15 14 2.5 74 80 4 25
P
(Starting
10/4/10)
380 – 415 50/60 3 3 8 15 14 2.5 65 70 4 25
150
Q 200 – 240 50/60 3 3 16 20 12 4
NOT AVAIL ABLE
R
(Through
10/1/10)
380 – 480 50/60 3 3 11 15 14 2.5
N
(Starting
10/4/10)
440 – 480 50/60 3 3 11 15 14 2.5
P
(Starting
10/4/10)
380 – 415 50/60 3 3 11 15 14 2.5
* NOTE: Wire sizing listed in this table is based on Article 310, Table 310.16 of the NEC; at 104°F (40°C) ambient
temperature. Follow your local electrical codes. Use only copper conductors, rated for 194ºF (90°C) or higher, type
THHN or better. No more than three current carrying conductors per raceway. Contact your local Authority having
jurisdiction if you have questions. Circuit breakers should be UL 489 listed or better. Single phase circuit breakers
for single phase machines only; three phase circuit breakers for all others.
** M30 Control Models only.
Table 10
Voltage Designation Non-Electric Heat
Machines (Standard)
Electric Heat Machines
Model
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Breaker
*AWG
*mm
2
Full Load
Amps
Breaker
*AWG
*mm
2