Alliance Laundry Systems LES33A Clothes Dryer User Manual


 
12
504607
Electrical Requirements . . .
(Electric Dryers)
NOTE: The wiring diagram is located inside the
control hood.
Grounding Instructions
This dryer must be connected to a grounded metal,
permanent wiring system; or an equipment-grounding
conductor must be run with the circuit conductors and
connected to the equipment-grounding terminal or lead
on the dryer.
To reduce the risk of fire, electric shock,
serious injury or death, all wiring and
grounding MUST conform with the latest
edition of the National Electrical Code,
ANSI/NFPA 70, or the Canadian Electrical
Code, CSA C22.1, and such local
regulations as might apply. It is the
customers responsibility to have the wiring
and fuses checked by a qualified electrician
to make sure your home has adequate
electrical power to operate the dryer.
W113
WARNING
D003IE3A
POWER SUPPLY POWER SUPPLY
3-WIRE GROUNDED NEUTRAL
120/240 VOLT, 60 HERTZ AC 1 PHASE
SERVICE ENTRANCE SWITCH BOX
(SEE NOTE BELOW)
NEUTRAL WIRE NEUTRAL WIRE
METALLIC OR
NON-METALLIC
SHEATHED CABLE
(COPPER WIRE
ONLY)
PIGTAIL
TO DRYER
(SEE NOTE BELOW)
NEUTRAL
L1 L2
PIGTAIL CONNECTION
L1 L2
DIRECT CONNECTION
NEUTRAL
WALL
RECEPTACLE
INTERMEDIATE
FUSE BOX
(MAY BE
OMITTED IF
SERVICE
ENTRANCE
BOX IS FUSED)
INTERMEDIATE
SHUT-OFF BOX
(MAY OR MAY
NOT BE FUSED)
A typical
30-Amp
Three-wire
Receptacle
NEMA Type
10-30R
30 AMPERE FUSES OR
CIRCUIT BREAKER
TERMINAL BLOCK
IN DRYER
120 ± 12
VAC
240 ± 12
VAC
120 ± 12
VAC
NOTE: The power cord (pigtail) is NOT supplied with the
electric dryer. Type of pigtail and gauge of wire must conform
to local codes and instructions.
The method of wiring the dryer is optional and subject to local
code requirements.
NOTE: Connect the dryer to the power supply with the
MAXIMUM RATED VOLTAGE listed on the nameplate.
NOTE: Use COPPER WIRE only.
Shorter than 15' (4.5 m) use 10 A.W.G.
Longer than 15' (4.5 m) use 8 A.W.G.
120 ± 12
VAC
A typical 30-Amp
Four-wire Receptacle
240 ± 12
VAC
120 ± 12
VAC
120 ± 12
VAC
120 ± 12
VAC
D006IE1F