Engineering Data : Schematic
9
NOTE
1 Use this bulletin for preliminary layouts only. Obtain
current drawings from your Marley sales representative. All
table data is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia. M connection located on the side of the tower. A 3" M
drain connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H A Weight/Cell
Heaviest
Section
MD5008MAC2L
165
5.5 80
3526 2413 3072 1723 891
MD5008MLC2L 165 5.5 79
MD5008NAC2L 179 7.5 81
MD5008NLC2L 179 7.5 79
MD5008PAC2L 202 11 81
MD5008PLC2L 202 11 80
MD5008QAC2L 217 15 81
MD5008QLC2L 217 15 80
MD5008MAD2L 180 5.5 80
3831 2718 3197 1848 957
MD5008MLD2L 180 5.5 79
MD5008NAD2L 196 7.5 81
MD5008NLD2L 196 7.5 79
MD5008PAD2L 222 11 81
MD5008PLD2L 222 11 80
MD5008QAD2L 239 15 81
MD5008QLD2L 239 15 80
MD5008MAF2L 188 5.5 80
4136 3023 3323 1974 1083
MD5008MLF2L 188 5.5 79
MD5008NAF2L 205 7.5 81
MD5008NLF2L 205 7.5 79
MD5008PAF2L 234 11 81
MD5008PLF2L 234 11 80
MD5008QAF2L 251 15 81
MD5008QLF2L 251 15 80
MD5008 MULTICELL