MD Cooling Tower
/
Engineering Data : Schematic
21
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
3 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia.
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H A Weight/Cell
Heaviest
Section
MD5016PAC4B
317
11 79
4801 3091 5933 3353 1710
MD5016PLC4B 320 11 78
MD5016QAC4B 345 15 80
MD5016QLC4B 348 15 79
MD5016RAC4B 369 18.5 80
MD5016RLC4B 372 18.5 79
MD5016SAC4B 390 22 81
MD5016SLC4B 394 22 80
MD5016PAD4B 350 11 79
5106 3396 6217 3636 1874
MD5016PLD4B 353 11 78
MD5016QAD4B 383 15 80
MD5016QLD4B 384 15 79
MD5016RAD4B 410 18.5 80
MD5016RLD4B 412 18.5 79
MD5016SAD4B 436 22 81
MD5016SLD4B 437 22 80
MD5016TAD4B 475 30 82
MD5016TLD4B 471 30 80
MD5016PAF4B 368 11 79
5410 3701 6448 3868 2105
MD5016PLF4B 370 11 78
MD5016QAF4B 403 15 80
MD5016QLF4B 401 15 79
MD5016RAF4B 431 18.5 80
MD5016RLF4B 431 18.5 79
MD5016SAF4B 460 22 81
MD5016SLF4B 459 22 80
MD5016TAF4B 500 30 82
MD5016TLF4B 493 30 80
MD5016 FOUR CELL QUAD