Date: August 31, 2007 ATT-TP-76450, Issue 9
Copyright ©2004 – 2006, AT&T Knowledge Ventures
All rights reserved
Page 17
5.7 Minimum Distance Between Connector Housing and 90 Degree Bend
Minimum Fiber distance away from a connector housing to bend 90 degrees shall be 3.75-
inches. See Figure 5–1.
Figure 5-1
1.5" Radius
3.75"
2.25"
1.5" Radius
3.0
"
D
i
a
meter
5.8 Space Between Door/Panel and Fiber Connector
To avoid pinching or reduction of minimum fiber bend radius the minimum distance between the
fiber connector and any door/panel cover shall be a minimum of 3.75 inches.
See Figure 5-1
5.9 Standard Fiber Connector
The AT&T standard fiber connector shall be SC-UPC single mode or LC-UPC single mode type
connector. Application of connector type shall be determined by equip design or manufacturer.
5.10 Alternative FTTP Fiber Connector
The AT&T alternative fiber connector for FTTP shall be SC-APC, SingleMode, 8-degree, keyed
type connector.
5.11 FiberOptic Cable Mode
Central Office fiber optic cable shall be SingleMode.
Customer Premises or IXC fiber optic cable may be SingleMode or Multimode.
SONET services fiber optic cable shall be SingleMode.
5.12 Fiber Transmission Material
Fiber transmission material shall be glass, not plastic or any other material not specifically pre-
approved by AT&T NP&E Staff.