Maytag MDG-75 Washer/Dryer User Manual


 
20
2. Electrical Service Specifications
a. Gas ONLY
IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact the
factory.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the back side of the top front control/service door. In the case of 208 VAC
or 240 VAC, the supply voltage must match the electric service specifications of the
data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: The manufacturer reserves the right to make changes in specifications at any time without
notice or obligation.
MDG-75 (Gas)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTE: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
B. Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify correct
breaker size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
Dual Element
Time Delay
CIRCUIT
BREAKER
120 (60 Hz) 2 13 * 20 20
208 (60 Hz) 2 8 * 12 15
208 (60 Hz) 3/4 5 * 8 15
240 (50/60 Hz) 2 7 * 12 15
380-400 (50 Hz) 3/4 3 * 5 15
416 (50 Hz) 3/4 3 * 5 15
460 (60 Hz) 3/4 3 * 5 15
* AWG Stranded Wire Type ...size wire as per National Electrical Code or local codes.