Cissell L36URD36S Clothes Dryer User Manual


 
Page 23
Dryer Installation With Multiple Exhaust
For Exhaust Duct less than 14 feet and 2 elbows
equivalent and less than 0.3 inches static pressure.
DRYER EXHAUSTS
Area of section “A-A” must be equal to the sum of dryer exhaust pipes entering
multiple exhaust pipe. (See chart below.)
MODELS: L28FD30, L28US30, L36FD30, L36UR30, L36CD36, L44FD42
MODELS: L28CD30, L28UR30, L36CD30, L36UR30, L36CD36, L44FD42
MODELS: L44CD42, L50CD42
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 9 11 12 14 15 16 17 18 19 20 21 22 23 23 24 25 26 26 27 28 28 29 30
15 23 27 30 35 38 41 43 46 48 51 53 56 58 58 61 63 66 66 68 71 71 73 76
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
8 12 14 16 18 20 22 23 24 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
20 30 35 41 46 51 56 58 61 66 68 71 73 76 78 81 84 86 89 91 94 97 99 100
1 2 3 4 5 6 7 8 9 10 11 12
12 17 21 24 27 30 32 34 36 38 40 42
30 43 53 61 68 76 81 86 91 97 100 106
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
AUTOMATIC ELECTRICAL CONTROL FOR EXHAUST FAN
For one or more dryers to start fan.
Exhaust
Booster Fan
Power Supply
to Fan
Relay Coils
Start and Stop
Switches on
Dryers
No. of Dryers
Duct Diameter
(in inches)
(in CM)
No. of Dryers
Duct Diameter
(in inches)
(in CM)
No. of Dryers
Duct Diameter
(in inches)
(in CM)