20
2. Electrical Service Specifications
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that
is affixed to the back of the dryer, at the upper right hand corner. In the case of
208 VAC or 240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically
VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or
obligation.
MLG-82 (Gas)
MLS-82 (Steam)
ELECTRIC SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTE: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct
breaker size according to appliance amp draw rating and type of breaker used.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
CIRCUIT
BREAKER
60 Hz 50 Hz
208 3 13.2 -- #14 25
240 3 12.2 14 #14 25
380 3 -- 7.3 #14 15
416 3
--
7.1 #14 15
460/480 3 6.6 -- #14 15
* AWG Stranded Wire Type for individual lengths less than 100 feet.