VERTICAL VENTING
When vertical single 10-inch (25.4 cm) venting is used, the ductwork from the dryer to the outside outlet cannot
exceed 40 feet (12 meters), refer to Illus. B below. This calculation compensates for the use of a maximum of
three (3) elbows including the two (2) elbows creating the 180° (turned downward) outside outlet.
Illus. B
If the length of the duct run or quantity of elbows used exceeds the above noted specifications, the cross section
area of the ductwork must be increased in proportion to the number of elbows or duct run added.
IMPORTANT: For extended ductwork runs, the cross section area of the duct can only be increased
to an extent. For extended ductwork runs, a professional heating, venting, and air
conditioning (HVAC) firm should be consulted for proper venting information.