American Dryer Corp. D-40 Clothes Dryer User Manual


 
13
SINGLE DRYER VENTING
IMPORTANT: For exhaust duct runs over 20 feet (6.1 meters) a minimum size of 10-inches (25.4
cm) must be used.
HORIZONTAL VENTING
When a single 8-inch (20.32 cm) horizontal vent is used, the ductwork to the outlet cannot exceed 20 feet (6.1
meters), refer to Illus. A below. This calculation of 20 feet (6.1 meters) compensates or allows for the use of
a maximum of only one (1) elbow, (which is the outside outlet protection).
Illus. A