American Dryer Corp. ADH-170 Clothes Dryer User Manual


 
22 American Dryer Corp. 113247-3
ADEH-75 Electric Models Only
All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.
* Customer must contact factory to special order 3-wire systems. 8/15/07
ADEH-170 Electric Models Only
Available upon request. Contact the factory.
Grounding
A ground (earth) connection must be provided and installed
in accordance with state and local codes. In the absence of
these codes, grounding must conform to applicable
requirements of the National Electrical Code ANSI/NFPA NO.
70-LATEST EDITION, or in Canada, the installation must
conform to applicable Canada Standards: Canadian Electrical
Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.
The ground connection may be to a proven earth ground at
the location service panel.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
60 kW
380 4* 100 125
416 4* 91 125
480 3 80 100
600 3 64 80
72 kW
208 3 214 300
240 3 188 250
230 3 198 250
380 3 118 150
380 4* 118 150
400 4* 113 150
416 4* 108 150
460 3 98 125
480 3 94 125
575 3 78 100
75.6 kW
440 3 102 150
* Customer must contact factory to special order 3-wire systems. 8/15/07
ADEH-120 Electric Models Only
All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
30 kW
208 3 91 125
230 3 83 125
240 3 79 100
380 3 48 60
380 4* 54 70
400 4* 51 70
416 4* 50 70
460 3 40 50
480 3 39 50
575 3 33 50
36 kW
208 3 108 150
230 3 98 125
240 3 94 125
380 3 58 80
380 4* 63 80
400 4* 60 80
416 4* 58 80
460 3 48 60
480 3 46 60