American Dryer Corp. AD-120ES II Clothes Dryer User Manual


 
24
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side panel/wall area behind the control door. In the case of 208
VAC or 240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.
WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
ADE-120 II (72 Kw Electric)
Reversing, 3ø
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC and 240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For
others, calculate/verify correct breaker size according to appliance amp
draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
OVEN SIZE
(Kw)
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
60 Hz 50 Hz
72 208 3 212 ---
72 240 3 186 190
72 380-400 3 --- 117
72 380-400 4 --- 117
72 416 3 --- 108
72 416 4 --- 108
72 460/480 3 97 ---
72 575/600 3 78 ---