American Dryer Corp. AD-115ES II Clothes Dryer User Manual


 
27
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side panel behind top/access control door. In the case of 208 VAC
or 240 VAC, the supply voltage must match the electric service specifications of the
data label exactly.
WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
IMPORTANT: 380, 400, and 416 Volt dryers are built 4-wire only. Customer must contact the
factory to special order 3-wire systems.
ADE-115ES (72 Kw Electric Oven) Reversing, 3ø Motor
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES
: A.When fuses are used they must be dual element, time delay, current limiting, class RK1or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.
B. Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
OVEN SIZE
(Kw)
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
60 Hz 50 Hz
Dual Element
Time Delay
72 208 3 214 -- * 300 300
72 240 3 188 190 * 250 250
72 380 4** -- 118 * 150 150
72 400 4** -- 112 * 150 150
72 416 4** -- 108 * 150 150
72 460 3 98 -- * 125 125
72 480 3 94 -- * 125 125
72 575 3 78 -- * 100 110
*AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.
(Motor lead wire is recommended.)
**3-wire available.