American Dryer Corp. AD-115ES II Clothes Dryer User Manual


 
25
2.
Electrical Service Specifications
*AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.
(Motor lead wire is recommended.)
** 3-wire available.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side panel behind top/access control door. In the case of 208 VAC
or 230 VAC, the supply voltage must match the electric service specifications of the
data label exactly.
WARNING: 208 VAC AND 230 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
IMPORTANT: 380, 400, and 416 Volt dryers are built 4-wire only. Customer must contact the
factory to special order 3-wire systems.
ADG-115ES Reversing, 3ø M otor (Gas)
ADS-115ES Reversing, 3ø M otor (Steam)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC and 230 VAC ARE
NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1
or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or
National Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw rating and type of
breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
208 3 14.5 -- * 20 20
240 3 14.6 16.4 * 20-25 20-25
380 4** -- 8.7 * 15 15
400 4** -- 8.5 * 15 15
416 4** -- 8.4 * 15 15
460/480 3 7.8 -- * 15 15
575 3 5.8 -- * 15 15