American Dryer AD-120ES Clothes Dryer User Manual


 
23
* AWG Stranded Type Wire ... for individual lengths less than 100 feet.
(Motor lead type wire is recommended)
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the back of the dryer, at the upper right hand corner. In the case of
208 VAC or 240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
WARNING: 208 VAC and 240 Volts ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or
obligation.
ADE-120ES (72 Kw Electric) Reversing, 3ø
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3Ø dryers must be 3-pole type.
OVEN SIZE
((Kw)
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay60 Hz 50 Hz
72 208 3 214 --- 4/0 300 300
72 240
3
186 187 3/0 250 250
72 380
3
117 117 1 150 150
72 380 4 117 117 1 150 150
72 416 3 --- 107 2 150 150
72 416 4 --- 107 2 150 150
72 480 3 98 --- 3 150 125
72 480
4
98 --- 3 150 125
72 575/600 3/4 79.4 --- 4 100 110