American Dryer AD-120ES Clothes Dryer User Manual


 
13
D. FRESH AIR SUPPLY
When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and
exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the
make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and
sail switch "fluttering" problems may result, as well as premature motor failure from overheating.
Air supply (make-up air) must be given careful consideration to assure proper performance of each dryer. An
unrestricted source of air is necessary for each dryer. An airflow of 2,150 cfm (cubic feet per minute) must be
supplied to each gas dryer and electric dryer with a 72 Kw oven, 2,500 cfm to each electric dryer with a 80 Kw
oven, and 2,750 cfm for each steam dryer. As a general rule, an unrestricted air entrance from the outdoors
(atmosphere) of a minimum of three (3) square feet is required for each gas dryer and 72 Kw electric dryer and
a minimum of five (5) square feet for each steam dryer and 80 Kw electric dryer.
To compensate for the use of registers or louvers used over the openings, this make-up air area must be increased
by approximately thirty-three (33) percent. Make-up air openings should not be located in an area directly near
where exhaust vents exit the building.
It is not necessary to have a separate make-up air opening for each dryer. Common make-up air openings are
acceptable. However, they must be set up in such a manner that the make-up air is distributed equally to ALL the
dryers.
EXAMPLE: For a bank of six (6) gas dryers, two (2) openings measuring 3 feet by 3 feet
(9 square feet) is acceptable.
Allowances must be made for remote or constricting passageways or where dryers are located at excessive
altitudes or predominantly low pressure areas.