Alliance Laundry Systems HC80VNV Washer User Manual


 
Programming
11
F232141
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Programming Cycle Segments
NOTE: Each cycle program can be customized
within the 11 program segments contained in a
cycle. A time must be entered for each segment. To
skip a segment or spin, set the time to “00” and
press Start (#) key. Refer to Table 3 for time
parameters.
NOTE: Spin times in cycle segments 1 – 10 are
entered in seconds (30 to 240), and time for final
spin in segment 11 is entered in minutes (1 to 10).
6. Press Up (arrow) key until display shows
segment to be edited. Press Start (#) key.
7. Use Up or Down (arrow) key to select Segment
Time. Set this value to “00” to skip segment.
Press Start (#) key.
8. If Temperature-Controlled Fill Setup Option is
enabled, display will show “tFIL”. Press
Start (#) key.
9. Use Up or Down (arrow) key to select Fill
Temperature: Cold (“CFIL”), Hot (“HFIL”),
Warm (“bFIL”) or Auxiliary (“AFIL”). Press
Start (#) key.
NOTE: An auxiliary fill is available only if
SUP5”/“AFIL” setup option is set to “AFIL”.
10. Use Up or Down (arrow) key to select Fill Level:
Low (“Lo”), Medium (“nEd”) or High (“HI”).
Press Start (#) key.
11. Use Up or Down (arrow) key to select Supply
Option. Refer to Table 4.
12. Press Start (#) key.
13. Use Up or Down (arrow) key to select Segment
Temperature: 75° to 200°F or 25° to 93°C
. Set
this value to zero to disable auxiliary heat and
temperature-controlled fill. Press Start (#) key.
NOTE: Only available if Temperature-Controlled
Fill or Auxiliary Heat Setup Option is enabled.
Time Parameters
Segment Minimum Maximum
PreWash “
PrE 2 minutes 30 minutes
Wash “
UASH 2 minutes 20 minutes
Fill 1 – Fill 9
FIL1”... “FIL9
2 minutes 15 minutes
Intermediate Spin 30 seconds 240 seconds
Final Spin 1 minute 10 minutes
Table 3
Supply Options
Display Supply
SUP0 No Supply
SUP1 Supply 1
SUP2 Supply 2
SUP3 Supply 3
SUP4 Supply 4
SUP5 Supply 5*
SUP6 Supply 1 and 5*
SUP7 Supply 3 and 4
*This is available only if the “
SUP5”/“AFIL” setup
option is set to “
SUP5”.
Table 4
To prevent personal injury, avoid contact
with inlet water temperatures higher than
125° Fahrenheit (51° Celsius) and hot
surfaces.
W748
WARNING