Chapter 5: Using the Web Interface
77
3. Selectthethresholdfromtheseconddrop‐downlistintheEvent
fieldasshownbelow.Thelistofthresholdswillvarydependingon
whatwasselectedinthefirstdrop‐downlist.
4. SelectanEventDirectionfromthethirddrop‐downlist.
• IfsettoAssert,thisalertwillonlytriggerwhenameasuredvalue
movespastacriticalthreshold(eitheraboveanuppercritical
threshold,orbelowalowercriticalone).
• IfsettoDeassert,thisalertwillon
lytriggerwhenameasuredvalue
returnstonormalfromacriticalstate(eitherbelowanuppernon‐
criticalthreshold,orabovealowernon‐criticalone).
• IfsettoAssert&Deassert,thisalertwilltriggerwhenameasured
valuecrossesanythresholdstate.
1. Selectapolicyfromthedr
op‐downlistinthePolicyfield.
2. ClickAdd.Thealertisaddedtothesystem.
Note:Nopoliciesappearinthisdrop‐downlistuntilyoucreate
them.Referto“CreatingAlertPolicies(onpage78)”sectionfor
instructions.
IfanEnvironmentalTemperatureorHumiditysensorisselected,an
eventwillbecreatedforeachlogicalTemperatureorHumidity
sensor.Theseeventalertscanbedeletedsothatonlytheonesyou
wantarepresent.