162 VIX IM MICROSTEPPER INDEXER DRIVE USER GUIDE
RFS
Return to factory settings
Syntax Units Range of ‘n’ Default See also
aRFS - - - SV
Description Issuing an RFS command initialises the controller to factory default settings.
The drive must be de-energised (OFF) for RFS to be executed.
Factory settings must be saved using the SV command before they take
effect.
The default settings are:
All labels cleared, all outputs set to logic low.
Note: the RFS state of ARM is start disabled, fault enabled (ARM01).
Properties
Immediate, can’t be used in labelled block, saved by SV
Example 1LIMITS(3,0,0,900) ;define limits
1RFS ;return to factory settings
1SV ;save factory settings
1LIMITS ;report limits
*LM0 TP1 M0 AD 200