3-4SectionWiring and Connections
23
3-4-2 Power Supply Wiring
Applicable Power Supply Use a power supply that conforms to specifications of at least 24 VDC and 3.5 W.
OMRON’s S82K-00724 is recommended (input: 100 VAC; output: 24 VDC,
7.5 W).
Note The above power supply is for a case where the CompoBus/S Slave is sepa-
rated from the power supply. Refer to the CompoBus/S Operation Manual
(W266) when supplying power to the whole system including the Slave.
Wiring Connections Wire the power supply as shown in the following diagram.
+
24 VDC
Note Be sure to ground the ground terminal of the power supply.
3-4-3 CompoBus/S Transmission Line Wiring
Applicable Cable Be sure to use the specified cable, and do not mix flat cable and VCTF cable.
Cable Model number Specifications
Special-purpose flat cable XBIT-W10 4-conductor flat cable:
0.75 mm
2
VCTF cable --- 2-conductor Vinyl-clad
VCTF JIS C3306
VCTF 0.75x2C