Liebert 1010 Clothes Dryer User Manual


 
Site Preparation
11
Table 2 Condenser physical data
Model #
Number
of Fans
Number
of Circuits
Connection Size, OD, In.
Net Weight
lb (kg) Hot Gas Liquid
Standard Models
CS*083 1 1 7/8 5/8 295 (134)
CD*104 1 2 7/8 1/2 315 (143)
CS*104 1 1 1-1/8 5/8 315 (143)
CD*165 2 2 7/8 5/8 425 (193)
CS*165 2 1 1-1/8 7/8 425 (193)
CD*205 2 2 1-1/8 7/8 495 (225)
CS*205 2 1 1-1/8 7/8 495 (225)
CD*251 3 2 1-1/8 7/8 500 (227)
CS*251 3 1 1-3/8 1-1/8 500 (227)
CD* 308 3 2 1-3/8 1-1/8 670 (304)
CS*308 3 1 1-5/8 1-1/8 670 (304)
CD* 415 4 2 1-3/8 1-1/8 840 (381)
CS*415 4 1 1-5/8 1-1/8 840 (381)
CD*510 4 2 1-5/8 1-1/8 1188 (539)
CD*616 6 2 1-5/8 1-1/8 1380 (626)
CS*616
1
6 1 (2)1-5/8 (2)1-1/8 1380 (626)
CD*830 8 2 1-5/8 1-1/8 1750 (794)
CD*1010 8 2 2-1/8 1-5/8 2640 (1197)
Quiet-Line Models
DCS*063 1 1 1-1/8 5/8 315 (143)
DCD*063 1 2 7/8 1/2 315 (143)
DCS*119 2 1 1-1/8 7/8 425 (193)
DCD*119 2 1 1-1/8 7/8 425 (193)
DCS*127 2 1 1-1/8 7/8 495 (225)
DCD*127 2 2 1-1/8 7/8 495 (225)
DCS*143 2 1 1-1/8 7/8 515 (234)
DCD*143 2 2 1-1/8 7/8 515 (234)
DCS*214 3 1 1-5/8 1-1/8 840 (381)
DCD*214 3 2 1-1/8 7/8 840 (381)
DCS*286 4 1 2-1/8 1-1/8 1105 (501)
DCD*286 4 2 1-1/8 7/8 1105 (501)
DCD*409 6 2 1-5/8 1-1/8 1380 (626)
DCD*572 8 2 2-1/8 1-1/8 2430 (1102)
1. Interconnection piping (field-supplied and installed) required. Configure piping for parallel
refrigerant flow between condenser sections.