Carrier 38AKS008 Clothes Dryer User Manual


 
Table 5 Electrical Data
UNIT
38
NOMINAL VOLTAGE
(V-Ph-Hz)
VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY
MIN MAX RLA LRA FLA MCA MOCP
AK007
208/230-3-60 187 254 21.8 142 1.9 25.6 35
460-3-60 414 508 9.6 72 1.0 12.9 15
575-3-60 518 632 7.6 58 1.9 11.4 15
220-3-50 198 242 19.0 142 1.0 25.6 35
400-3-50 360 440 9.5 72 1.0 12.9 15
AK008
208/230-3-60 187 254 28.8 195 3.8 39.8 45
460-3-60 414 508 14.7 95 1.9 20.3 20
575-3-60 518 632 10.8 80 1.9 15.4 15
220-3-50 198 242 28.8 195 1.5 37.5 45
400-3-50 360 440 14.7 90 1.5 19.9 20
AK012
208/230-3-60 187 254 37.8 239 3.1 46.2 60
460-3-60 414 508 17.2 125 1.4 22.7 30
575-3-60 518 632 12.3 80 1.4 19.3 25
220-3-50 198 242 37.8 239 1.4 46.2 60
400-3-50 360 440 17.2 125 1.4 22.7 30
AKS008
208/230-3-60 187 254 31.5 160 3.1 42.5 50
380-3-60 342 418 19.0 75 2.2 26.0 35
460-3-60 414 508 15.7 80 1.4 21.0 25
575-3-60 518 632 12.6 64 1.4 17.2 20
220-3-50 198 253 31.5 160 1.4 42.5 50
400-3-50 342 460 15.7 80 1.4 21.0 25
AKS009
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
220-3-50 198 253 39.7 198 1.4 52.7 70
400-3-50 342 460 19.9 99 1.4 26.3 35
AKS012
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
220-3-50 198 253 39.7 198 1.4 52.7 70
400-3-50 342 460 19.9 99 1.4 26.3 35
LEGEND
CSA Canadian Standards Association
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code (U.S.A. Standard)
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
UL Underwriters’ Laboratories
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB =452 v
BC =464 v
AC =455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
(AB) 457 - 452 =5 v
(BC) 464 - 457 =7 v
(AC) 457 - 455 =2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance
7
% Voltage Imbalance =100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
3. The 575-v units are CSA only.
4. The 380 v, 60 Hz units and all 50 Hz units are
not
UL or CSAlisted.
7