Table 5 — Electrical Data
UNIT
38
NOMINAL VOLTAGE
(V-Ph-Hz)
VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY
MIN MAX RLA LRA FLA MCA MOCP
AK007
208/230-3-60 187 254 21.8 142 1.9 25.6 35
460-3-60 414 508 9.6 72 1.0 12.9 15
575-3-60 518 632 7.6 58 1.9 11.4 15
220-3-50 198 242 19.0 142 1.0 25.6 35
400-3-50 360 440 9.5 72 1.0 12.9 15
AK008
208/230-3-60 187 254 28.8 195 3.8 39.8 45
460-3-60 414 508 14.7 95 1.9 20.3 20
575-3-60 518 632 10.8 80 1.9 15.4 15
220-3-50 198 242 28.8 195 1.5 37.5 45
400-3-50 360 440 14.7 90 1.5 19.9 20
AK012
208/230-3-60 187 254 37.8 239 3.1 46.2 60
460-3-60 414 508 17.2 125 1.4 22.7 30
575-3-60 518 632 12.3 80 1.4 19.3 25
220-3-50 198 242 37.8 239 1.4 46.2 60
400-3-50 360 440 17.2 125 1.4 22.7 30
AKS008
208/230-3-60 187 254 31.5 160 3.1 42.5 50
380-3-60 342 418 19.0 75 2.2 26.0 35
460-3-60 414 508 15.7 80 1.4 21.0 25
575-3-60 518 632 12.6 64 1.4 17.2 20
220-3-50 198 253 31.5 160 1.4 42.5 50
400-3-50 342 460 15.7 80 1.4 21.0 25
AKS009
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
220-3-50 198 253 39.7 198 1.4 52.7 70
400-3-50 342 460 19.9 99 1.4 26.3 35
AKS012
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
220-3-50 198 253 39.7 198 1.4 52.7 70
400-3-50 342 460 19.9 99 1.4 26.3 35
LEGEND
CSA — Canadian Standards Association
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code (U.S.A. Standard)
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
UL — Underwriters’ Laboratories
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB =452 v
BC =464 v
AC =455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
(AB) 457 - 452 =5 v
(BC) 464 - 457 =7 v
(AC) 457 - 455 =2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance
7
% Voltage Imbalance =100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
3. The 575-v units are CSA only.
4. The 380 v, 60 Hz units and all 50 Hz units are
not
UL or CSAlisted.
7