American Dryer Corp. MLS-460 Clothes Dryer User Manual


 
50
4.
Front Panel Blue Light and Red Light ON
MLS-460 ON button does respond ...
a. PROBABLE CAUSES;
1) EMERGENCY STOP (E-Stop) BUTTONS 1, 2, and 3.
b. POSSIBLE SOLUTIONS;
1) Verify that ALL EMERGENCY STOP (E-Stop) buttons are pushed in.
EMERGENCY STOP 1 - main enclosed door
EMERGENCY STOP 2 - pendant control
EMERGENCY STOP 3 - rear control panel (2-door models only)
If ALL EMERGENCY STOP (E-Stop) buttons are disengaged, press ON located on the
main enclosure door.
If NO, go to section 3 on page 46
Does the system green ON light illuminate?
If not, check the EMERGENCY STOP (E-Stop) and drying system ON/OFF circuits. (Refer
to ladder diagram.)
5. Front Panel blue (main panel) light, red (sprinkler power) light, and green (control power)
light ON
The system has one or more of the following symptoms;
OPERATOR INTERFACE TERMINAL - no display or displays LINE FAULT message
PROGRAMMABLE LOGIC CONTROLLER (PLC) - no indicator lights ON
CONVENIENCE OUTLET - no power
HI-LIMIT CONTROLLERS (HLS1 and HLS2) - no display
a. PROBABLE CAUSES;
1) Fuse 7 -- PLC (Programmable Logic Controller) power
Fuse 8 -- 24 volt DC power
Fuse 9 -- convenience outlet
Fuse 10 - hi-limit controller power
2) Malfunctioning PLC (Programmable Logic Controller).