American Dryer Corp. ML-96D Clothes Dryer User Manual


 
20
Each dryer should be connected to an independently protected branch circuit. The dryer must be connected
with copper wire only. DO NOT use aluminum wire, which could cause a fire hazard. The copper
conductor wire or cable must be of proper ampacity and insulation in accordance with electric codes for
making ALL service connections.
NOTE: The use of aluminum wire will VOID THE WARRANTY.
IMPORTANT: Wiring diagrams are affixed to the inside at the top front control door and to the rear
upper back guard or panel.
2. Electrical Service Specifications
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side panel/wall area behind the control door. In the case of 208
VAC or 240 VAC, the supply voltage must match the electric service specifications
of the data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
MLG-96D
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)*
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
MINIMUM
WIRE SIZE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz 60 Hz 50 Hz
208 3/4
** 13.5 -- 25 --
240 3 ** 12.5 -- 25 --
380-400 3/4 ** -- 6.9 -- 15
416 3/4 ** -- 6.6 -- 15
460/480 3/4
** 6.8 -- 15 --
* Contact factory for information not listed.
** AWG Stranded Wire Type ... size wire as per National Electrical Code or local codes.