20 Maytag Co. 113395-6
2. Electrical Service Specifications
IMPORTANT: Figures shown are for reversing models.
MD-120 Gas
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
208 3ø 3 14.5 — 20
240 3ø 3 14.6 — 20
230 3ø 3 — 17.4 25
380 3ø 3 8.5 — 15
380 / 400 3ø 4* —8.7 15
416 3ø 4* —9.0 15
440 3ø 3 8.7 — 15
460 / 480 3ø 3 7.8 — 15
575 3ø 3 5.8 — 15
MD-170 Gas and Steam
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
208 3ø 3 28.3 — 50
240 3ø 3 26.7 — 45
230 3ø 3 — 31.9 50
380 3ø 3 16.2 — 25
380 / 400 3ø 4* — 16.1 25
416 3ø 4* — 16.0 25
440 3ø 3 14.4 — 20
460 / 480 3ø 3 13.9 — 20
575 3ø 3 11.4 — 20
* 3-Wire is available. 4/20/07
* 3-Wire is available. 4/20/07