American Dryer Corp. D120 Clothes Dryer User Manual


 
24
2.
Technical Data
a. Gas Specifications
* Measured at the gas valve pressure tap when the gas valve is on.
b. Gas Connections:
Inlet connection ---- 1-1/4” F.P.T.
Inlet supply size ---- 1-1/4” N.P.T. (minimum)
Btu/hr input --------- 415,000 (104,580 kcal/hr)
1) Natural Gas
Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure
must be consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches
(29.9 mb) water column (W.C.) pressure.
2) Liquid Propane (L.P.) Gas
Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so
that the gas pressure must be regulated upstream of the dryer. The pressure measured at each gas
valve pressure tap must be a consistent 10.5 inches (26.1 mb) water column. There is no regulator
or regulation provided in an L.P. dryer. The water column pressure must be regulated at the source
(L.P. tank) or an external regulator must be added to each dryer.
Shaded area is stated in metric equivalent
* Drill Material Size (D.M.S.) equivalents are as follows:
Natural Gas .................. #2 = 0.2210” (5.6134 mm).
Liquid Propane Gas ..... #30 = 0.1285” (3.2639 mm).
TYPE OF GAS
NATURAL LIQUID PROPANE
Manifold Pressure* 3.5 inches W.C. 8.7 mb 10.5 inches W.C. 26.1 mb
In-Line Pressure 6.0 - 12.0 inches W.C.
14.92 - 29.9 mb 11.0 inches W.C. 27.4 mb
Shaded areas are stated in metric equivalents
TYP E OF GAS
L.P.
Conversion Kit
Part Number
MODEL
NUMBER
BTU
Per Hour
Rating
kcal/hr
Rating
Natural Liquid Propane
Qty. D.M.S.*
Part
Number
Qty. D.M.S.*
Part
Number
D-120 415,000 104,580 3 #2 140839 3 #30 140819 882233