American Dryer Corp. AD-20 Clothes Dryer User Manual


 
22
3.
Piping Connections
ALL components/materials must conform to National Fuel Gas Code Specifications ANSI Z223.1-LATEST
EDITION, or in Canada, CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (Liquid
Propane [L.P.] Gas) or LATEST EDITION (for General Installation and Gas Plumbing), as well as local
codes and ordinances and must be done by a qualified professional. It is important that gas pressure
regulators meet applicable pressure requirements, and that gas meters be rated for the total amount of
ALL the appliance BTUs being supplied.
The dryer is provided with a 3/8-inch N.P.T. inlet pipe connection located at the right side of the base of the
dryer. The minimum pipe size (supply line) to the dryer is 3/8-inch N.P.T. For ease in servicing, the gas
supply line of each dryer must have its own shutoff valve.
IMPORTANT: The gas supply line to each dryer must be a minimum of 3/8-inch (9.5 mm). DO
NOT REDUCE THIS PIPE SIZE REQUIREMENT.
The size of the main gas supply line (header) will vary depending on the distance this line travels from the
gas meter or, in the case of L.P. gas, the supply tank, other gas-operated appliances on the same line, etc.
Specific information regarding supply line size should be determined by the gas supplier.
NOTE: Undersized gas supply piping can create a low or inconsistent pressure, which will result in
erratic operation of the burner ignition system.