The connection should be shielded in a liquid tight or approved exible conduit with proper
conductors of correct size installed in accordance with the National Electric Code or other
applicable codes. The connection must be made by a qualied electrician using the wiring diagram
provided with the washer-extractor, or according to accepted European standards for CE-approved
equipment.
Use wire sizes indicated in Table 3 through 7 for runs up to 50 feet.
Use next larger size for runs of 50 to 100 feet. Use two sizes larger for runs greater than 100 feet.
For personal safety and proper operation, the washer-extractor must be grounded in accordance
with state and local standards. If such standards are not available, grounding must conform to the
National Electric Code, article 250-95. The ground connection must be made to a proven earth
ground, not to a water pipe, gas pipe, or another metal pipe. Provide the necessary equipotential
connections according to the local electrical prescriptions.
GROUNDING INSTRUCTIONS
This appliance must be connected to a grounded metal, permanent wiring system; or an equipment-
grounding conductor must be run with the circuit conductors and connected to the equipment-
grounding terminal or lead on the appliance.
IMPORTANT: Alliance Laundry Systems Warranty does not cover components that fail as a
result of improper input voltage.