ADC AD-115ES Clothes Dryer User Manual


 
113202-10 www.amdry.com 19
Reversing, 3ø Motor (Electric)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
60 kW
208 3 181 * 250 250
230 3 167 * 200 200
240 3 159 * 200 200
380 4** 100 * 125 125
400 4** 95 * 125 125
416 4** 92 * 125 125
460 3 83 * 125 125
480 3 80 * 100 100
575 3 66 * 100 100
72 kW
208 3 214 * 300 300
230 3 197 * 250 250
240 3 188 * 250 250
380 4** 118 * 150 150
400 4** 112 * 150 150
416 4** 109 * 150 150
460 3 98 * 125 125
480 3 94 * 125 125
575 3 78 * 100 100
* AWG Stranded Wire Type; size wire as per National Electrical Code or local codes. (Motor lead wire is recommended.) 12/10/08
** 3-Wire is available.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label. In the
case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
WARNING: 208 VAC AND 230/240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
IMPORTANT: 380, 400, and 416 volt dryers are built 4-wire only. Customer must contact the
factory to special order 3-wire systems.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.