JKSSS+ Series - 38
JKSSS+ Series 2.3 - 4.2KV
5.1.4RelayAssignments(SetpointPage4)
O/L Trip Trip Only None None
S/C Trip Trip Only None None
Overcurrent Trip Trip None None
Stator RTD Trip None None None
Non Stator RTD Trip None None None
*G/F Hi Set Trip Trip None None
*G/F Lo Set Trip Trip None None
Phase Loss Trip Trip None None
Accel. Time Trip Trip Only None None
Start Curve Trip Trip Only None None
Over Frequency Trip None None None
Under Frequency Trip Trip None None
I*I*T Start Curve Trip None None
Learned Start Curve Trip None None
Phase Reversal Trip None None
Overvoltage Trip Trip None None
Undervoltage Trip Trip None None
Power Factor Trip None None None
Tach Accel Trip None None None
Inhibits Trip Trip None None
Shunt Trip None None None
Bypass Discrepancy None None None
External Input #2 None None None
Thermostat Trip None None
O/L Warning Alarm None None
Overcurrent AlarmAlarm None None
SCR Fail Shunt Alarm None None None
*Ground Fault AlarmAlarm None None
Under Current Alarm None None None
Motor Running AUX3 None None
Stator RTD Alarm None None None
Non-Stator RTD Alarm None None None
RTD Failure Alarm None None None
Self Test FailTrip None None
Thermal Register Alarm None None
Power Factor Alarm None None None
KW Demand Alarm None None None
KVA Demand Alarm None None None
KVAR Demand Alarm None None None
Amps Demand Alarm None None None
Timed Output None None None
Run Delay Time None None None
Level 2
Password Protection
None
Trip(AUX1)
Alarm(AUX2)
AUX3
AUX4
AUX5-8
Only Available in 8 Relay
System
Notes:
AUX1 to AUX4 are for Factory
Use only. Do not change!
Only AUX 5 - 8 are used in the
2nd & 3rd relay assignments.