Data composition of output instance 100
Byte bit Specifications 0 1 Supplement
0 0 Preset speed #1*
1
0 1 Preset speed #2*
1
0 2 Preset speed #3*
1
0 3 Preset speed #4*
1
Preset speed OFF: 0000,
Preset speed #1-#15: 0001 to 1111
A combination of 4 different bits is used
to select a preset speed from among
preset speed operation OFF and preset
speed #1 to #15.
0 4
Motor #1/#2
(THR2 selection)
Motor #1
(THR1)
Motor #2
(THR2)
Used to select a motor
electronic-thermal protection level.
0: Protection level #1 (thr)
1: Protection level #2 (f173)
0 5 PI control Normal operation PI control off -
0 6
Acceleration/
Deceleration
#1/#2 selection
(AD2 selection)
Acceleration/
Deceleration #1
(AD1)
Acceleration/
Deceleration #2
(AD2)
Used to select acceleration/deceleration
time.
0: acc, dec
1: f500, f501
0 7 DC braking OFF
Forced DC
braking
If “1” is specified, db is displayed.
1 0 JOG run*
2
OFF JOG run
If “1” is specified, operation is performed
at the frequency specified with f260
(jog run frequency).
1 1
Forward run/
Reverse run
Forward run Reverse run -
1 2 Run/Stop Stop Run -
1 3 Coast stop
Ready for
operation
Coasting -
1 4 Emergency stop OFF Emergency stop If “1” is specified, e tripping can occur.
1 5 Reset OFF Reset Enabled only in the event of tripping
1 6 Frequency link OFF Priority
Enabled regardless of the setting
of fmod
1 7 Command link OFF Priority
Enabled regardless of the setting
of cmod
*1: Preset speed operation can be performed at up to 15 different frequencies (preset
speed operation frequencies #1 to #15) specified by combining preset speed 1 to
preset speed 4. To perform preset speed operation, the “Command priority” option
and the “Run/Stop” bit must be set to 1.
Example: To run the motor in the reverse direction at preset speed operation
frequency #7 (sr7)
“10000110 00000111 = 0x8607 (hexadecimal)
If one of the bits for “Preset speed #1” to “Preset speed #4” is set to 1, priority is given
to preset speed operation even though the “
Frequency link” bit is set to 1, and therefore
operation is not performed by “
Frequency link”.
*2: Jog operation has higher priority than preset speed operation. If the operation
frequency is higher than the jog run frequency, however, jog operation is not carried
out.