Inallcases,motorsaredesignedforoperating
voltagesplusorminus10%ofthenormalrating
(seeSPECIFICATIONS).
1.Verifythevoltageandfrequencyattheoutlet
matchthespecicationsonthepumpmotor
decal.VerifytheON/OFFswitchisinthe
OFFpositionbeforeyouplugthepump
intoanoutlet.Verifythegasballastvalveis
closed.Removeanddiscardtheexhaustplug
fromtheendofthepump’shandle.
2.Thepumpisshippedwithoutoilinthe
reservoir.Beforestartingthepump,llwith
oil.RemovetheOILFILLcap(blackplastic
plugdirectlyinfrontofthehandle),andadd
oiluntiltheoiljustshowsinthebottomofthe
sightglass.Theapproximateoilcapacityof
thepumpis375milliliters.
3.ReplacetheOILFILLcapandremovethecap
fromoneoftheinletports.TurntheIso-Valve
toOPEN.TurnthemotorswitchON.When
thepumprunssmoothly,turntheIso-Valve
toCLOSEDandreplacethecapontheinlet
port.Thismaytakefromtwoto30seconds,
dependingontheambienttemperature.After
thepumprunsforapproximatelyoneminute,
checkthesightglassforcorrectoillevel—
oilshouldbeevenwiththesightglassOIL
LEVELline.Addmoreoilifnecessary.
Whenthepumpisrunning,theoillevel
shouldbeevenwiththelineonthesight
glass.Underllingwillresultinpoorvacuum
performance.Overllingcanresultinoil
blowingfromtheexhaust.
Yourpumpisnowreadytoevacuateair
conditioningandrefrigerationsystems.Follow
normalserviceproceduresandtheA/C-R
manufacturer’sinstructionsforconnectionstothe
system.
Before using your vacuum pump
Operating Manual
4
Emerson MotorsGeneral Electric Motors
CAUTION! Before connecting the vacuum pump
to an A/C-R system, remove refrigerant from the
system in an accepted manner. Damage to the
pump may occur if evacuation is started while
the system is under high pressure. Robinair
recommends use of our Refrigerant Recovery
and Recycling equipment.
Wiring Instructions:
Thisvacuumpumpfeaturesdualvoltageranges.
Beforeoperatingthepump,readandfollowthese
rewiringinstructions(ifnecessary)tobesureyour
pumpiswiredfortheappropriatevoltage.
CAUTION! Unplug the unit before
beginning any service work. Incorrect
use or connections can cause electrical
shock. Only qualied personnel should
perform service work.
Thisvacuumpumpisfactorywiredforahigh
voltagerangeof220to250volts.Towirethe
switchforalowvoltagerangeof110voltsto115
volts,followthesesteps:
1.
DisconnecttheunitfromtheACpowersource.
2.Loosenthescrewsontheplateattherearof
themotor,andcarefullymovetheplateaside
tocleartheopening.
3.Disconnecttheleadsandreconnectforlow
voltage,followingthediagramandchart.
(Highvoltageconnectionsarealsoshownif
youwanttorewireinthefuture.)
4.Verifyconnectionsaresecureandthere
arenoshortcircuits.Verifythegrounding
connectoriscorrectlyconnected.
5.Re-installtheplateontherearofmotorwith
thescrewswhichwereloosenedinStep2.
IMPORTANT: Checkforshortcircuitsusinga
continuitytesterbeforereconnectingtotheAC
powersource.
— EMERSON —
INTERNAL VOLTAGE CONNECTION
MOTOR LOW HIGH
LEAD VOLTAGE VOLTAGE
BROWN 3 6
WHITE 4 3
BLACK 2 3
INST0350
NOTE: EXTERNAL POWER LEADS ARE ALWAYS
CONNECTED TO TERMINALS 1 AND 4.