11 - 10 Treatment of Fixed Amount Circulation Malfunction
Factory Setting: 00
Settings
00: Turn off all motors
01: Turn off AC drive
๎€‰ This parameter determines treatment of AC drive malfunction during fixed amount
circulation.
๎€‰ When AC drive occurs power circuit malfunction to make auxiliary power disable and
microprocessor canโ€™t work, all output will close automatically.
11 - 11 Stop Frequency of Auxiliary Motor
Factory Setting: 0.00
Settings 0.00~120.00Hz Unit: 0.01Hz
๎€‰ If output frequency of AC drive is less than or equal to this parameter when AC drive is fixed
amount circulation
(11-01=02) or fixed amount (11-01=03), AC drive will make motor stop in
sequence.