RTU Open 61
– The usage of Input 8. You must also set
Input 8 Switch Configuration
Options:
.
– The input is not used.
– Indicates enthalpy status (high or low).
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
D:
– Sets occupancy using a hardware contact.
R:
Enthalpy Switch
No Function
Enthalpy Switch
Fan Status
Filter Status
Remote Occupancy
Door Contact
D: – The normal (de-energized) state for the set of contacts
terminated at Input
R:
NO
NO/NC (normally
open/normally closed)
– The usage of Input 9. You must also set
Input 9 Switch Configuration
Options:
.
– The input is not used.
– Indicates high humidity condition.
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
D:
– Sets occupancy using a hardware contact.
R:
Humidistat
No Function
Humidistat
Fan Status
Filter Status
Remote Occupancy
Door Contact
D: – The normal (de-energized) state for the set of contacts
terminated at Input
R:
NO
NO/NC (normally
open/normally closed)
D: - The type of local space temperature sensor.
R:
T55
T55
T56 (Use for T59)
SPT Sensor
None
D: – If using a T55, T56, or T59 sensor, this is the amount of time
that the controller runs in the occupied mode when a user presses the sensor's override
button for 1 to 10 seconds.
R:
1 hr
0 to 24 hours
D: – A calibration offset value to allow the local space temperature
sensor to be adjusted to match a calibrated standard measuring the temperature in the
same location.
R:
0°F
-9.9 to 10°F
Supply Air Temp Calibration
D: – A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
R:
0°F
-9.9 to 10°F
Outside Air Temp Calibration
D: – A calibration offset value to allow the outside air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
R:
0°F
-9.9 to 10°F
Setpoints