OPERATING INSTRUCTIONS
The inner housing assembly must be installed and
the power pack / door assembly to the air cleaner
must be fully closed.
The unit should be plugged in and the power
switch on the air cleaner door turned on. There are
no other controls or settings required.
When the system blower turns on, the air cleaner
will turn on and a green light located on the air
cleaner door will turn on. After the system blower
has turned off, the green light will turn off.
TROUBLE SHOOTING GUIDE
When the air cleaner is operating
correctly and the following
conditions are met, the green
light on the door will be on:
• The air cleaner is correctly
assembled and installed.
• The power pack / door
assembly is fully closed.
• The unit is plugged into
an EAC controlled 120 VAC
outlet.
• The switch is in the ON
position.
• The furnace/air handler
blower is running.
If those conditions are met and
the green light does not come on,
the air cleaner circuit is not being
activated. If the green light blinks
at approximately one-minute
intervals, the air cleaner circuitry
is attempting to turn on, but is
quickly turning off due to either
an over-current condition or
because arcing is occurring
between components. Check
the inner assembly as follows:
1. Turn the furnace/air handler blower off.
2. Turn the air cleaner off.
3. Unplug the air cleaner.
4. Open the power pack / door assembly.
5. Remove the inner housing assembly.
6. Inspect components to ensure the following:
a. All components must be dry.
b. The ionizer frame-grounding clip must be
in contact with the pre-filter. See Figure 11.